Both switches and transmitters are available in a 19mm closed hole version and with split core opening for larger cables. With switches for point-monitored applications and transmitters for high accuracy analogue output, Bürkert caters to the complete application spectrum.
The AC current transmitter range is 10 .. 40V DC loop powered and offer three selectable ranges covering the range 0 to 200 amps. These transmitters work effectively in conjunction with a SCADA or DCS system as an analysis or preventative maintenance control loop.
| A200 Closed Hole |
 |
| SC200 Split Core |
|
AC current transmitters are frequently used in monitoring filling and pumping operations by measuring motor currents, delivering high accuracy 4 .. 20mA analogue output for ensuring engine protection. The versatile units monitor changing process variables such as level or viscosity to detect accurately out of limit conditions or end of process.
All AC Current Sensors have screw terminal connections for mounting and work in a wide range of ambient temperatures -10 .. 80°C. Response times for all units is less than 300 milliseconds, making the units ideal for high confidence equipment protection and monitoring applications.
The AC current switch units require no external power supply and monitor to 150 Amps, with adjustments by potentiometer. These 'trip condition' switches have a smart LED for visual status indication, with the LED indicator visually showing that the unit is off; that the process is within the acceptable range or that the sensor has tripped. Applications for the AC current switch include engine protection with single trip points; detecting broken belts and couplings and monitoring lighting signals with accuracy less than 1% of full scale.
Selection Guide & Datasheet Downloads:
AC Current Transmitters
| Model |
Selectable Range (Jumper) |
Configuration |
Max. Current |
| A200-1 |
Low: 0 .. 10A Med: 0 .. 20A High: 0 .. 50A |
Closed Hole Ø19mm |
200A Cont) |
| A200-2 |
Low: 0 .. 100A Med: 0 .. 150A High: 0 .. 200A |
Closed Hole Ø19mm |
1200A (15s) |
| SC200-1 |
Low: 0 .. 10A Med: 0 .. 20A High: 0 .. 50A |
Split Core 21mm² |
200A (Cont) |
| SC200-2 |
Low: 0 .. 100A Med: 0 .. 150A High: 0 .. 200A |
Split Core 21mm² |
1200A (15s) |
AC Current Switches
| Model |
Selectable Ranges |
Configuration |
Output Contact |
Adjustment |
| D100C |
1 .. 150 Amp AC |
Closed Hole Ø19mm |
300mA 120V AC/DC |
15 Turn Pot |
| D100C-SC |
1.5 .. 150 Amp AC |
Split Core 21mm² |
300mA 120V AC/DC |
4 Turn Pot |
Click here to order your copy of the Australia Select Price List, which includes the complete eLINE range. All eLINE units are ex-stock for immediate despatch.